Does the NFC permit branch circuits and feeders to be in the same raceway as service conductors for a short distance? If not, can they share the same pull box? The NEC prohibits branch circuits and feeders from being installed in the same raceway or cable assembly as service conductors. See Section 230.7. Two exceptions to this general rule permit grounding electrode conductors, supply-side bonding jumpers/conductors and load-management control conductors having overcurrent protection to be installed in service raceways. Article 230 is silent with respect to service conductors occupying the same pull box as other conductors. Perhaps public input is needed to provide clarity. Get involved in the process; you can change the Code.