首页> 外文期刊>Elektrotechnik und Informationstechnik >Experimental investigations to the jointresistance of bolted substation and transmission line connectors and its conformity to test standards
【24h】

Experimental investigations to the jointresistance of bolted substation and transmission line connectors and its conformity to test standards

机译:变电站与输电线路连接器螺栓连接电阻的试验研究及其与试验标准的符合性

获取原文
获取原文并翻译 | 示例

摘要

This paper summarizes the experimental investigations on joint resistance and current distribution of connections with straight connectors. Different sizes (2-4 covers) and types of contact surface (as cast, riffled) are reviewed. Connectors with 2 covers have the lowest joint resistance whereas connectors with 4 covers do have the best performance factor. The kind of contact surface does not affect the initial joint resistance. To compare these two conductor groove shapes long term tests are necessary. Calculations using a resistance network prove the measured initial joint resistances. The current distribution in the connector body is influenced insignificantly by the joint resistance. The more covers a connector possesses the longer is the estimated lifetime.
机译:本文总结了直连接器连接的接头电阻和电流分布的实验研究。审查了不同尺寸(2-4个覆盖层)和类型的接触面(铸造,浅口)。具有2个盖子的连接器的接头电阻最低,而具有4个盖子的连接器的性能系数却最好。接触表面的种类不影响初始接头电阻。为了比较这两个导体凹槽的形状,需要长期测试。使用电阻网络进行的计算证明了测得的初始接头电阻。连接器主体中的电流分布不受接头电阻的影响很小。连接器的覆盖层越多,估计寿命就越长。