首页> 外文期刊>Electric power systems research >Lightning overvoltages on complex low-voltage distribution networks
【24h】

Lightning overvoltages on complex low-voltage distribution networks

机译:复杂的低压配电网络上的雷电过电压

获取原文
获取原文并翻译 | 示例
获取外文期刊封面目录资料

摘要

This paper presents a theoretical investigation on lightning overvoltages on low-voltage (LV) networks installed in urban areas. The combined effect of lightning-induced voltages and transferred lightning surges through distribution transformers is taken into account. It is shown that an accurate estimate of lightning overvoltages on LV networks that have a neutral conductor grounded at the transformer pole require the consideration of the medium voltage line and its electrical connections with the LV line. It is also shown that if the stroke location is relatively close to the evaluated LV line it is possible to neglect the influence of other LV lines in the estimation of peak overvoltages on the connected loads. Finally, it is shown that load overvoltages are strongly dependent on the assumed load model, which suggests that simplified load models must be viewed with caution in studies of lightning overvoltages on LV networks.
机译:本文提出了对城市中安装的低压(LV)网络上雷电过电压的理论研究。考虑了雷电感应的电压和通过配电变压器传递的雷电浪涌的综合影响。结果表明,对中性导体在变压器极接地的LV网络上雷电过电压的准确估计,需要考虑中压线及其与LV线的电连接。还显示出,如果行程位置相对靠近评估的LV线,则在估计峰值过电压对连接负载的影响时,可以忽略其他LV线的影响。最后,表明负载过电压在很大程度上取决于假设的负载模型,这表明在研究LV网络上的雷电过电压时,必须谨慎考虑简化的负载模型。