摘要

In this article, the decoupled property of the recently developed so-called hybrid model is used to derive time-variant analytical waveforms of the phase voltage and the field current following the load-rejection test. In the proposed identification approach, these time-variant responses are fitted to actual data using the asymptotic weighted least squares estimator along with a Newton-type optimization algorithm to compute the 4-pole 1.5-kVA, 208-V, 60-Hz laboratory synchronous generator parameters. In order to assess the robustness of the proposed identification scheme more thoroughly, the synchronous generator estimated parameters were successfully applied at the cross-validation stage using the symmetrical three-phase short-circuits test data.
机译:在本文中,最近开发的所谓混合模型的去耦特性用于推导负载抑制测试后相电压和励磁电流的时变分析波形。在提出的识别方法中,使用渐近加权最小二乘估计器和牛顿型优化算法将这些时变响应拟合到实际数据,以计算4极1.5kVA,208V,60Hz实验室同步信号发电机参数。为了更全面地评估所提出的识别方案的鲁棒性,使用对称三相短路测试数据在交叉验证阶段成功应用了同步发电机估计参数。