Reactions between the liquid insulation and the copper conductors in power transformers and other electrical apparatus may lead to the formation of dissolved and suspended copper in the insulating oil. In this work a study concerning the correlation between the copper form and the dielectric properties of the fluid is presented. In particular, to determine the total copper content in oil and consequently to discriminate by subtraction the presence of particulate copper, we optimized a method of oil mineralization. Moreover, by filtering the oils with PTFE filters (0.45, 1 and 5 ;C;m), the dimension of suspended copper content has been quantified and discriminated from the dissolved one: in such way, we investigated the influence of particulate copper on the characteristics of the oils and we determined the physical form that mostly affect the dielectric properties.
机译:电力变压器和其他电气设备中液体绝缘层与铜导体之间的反应可能导致绝缘油中溶解和悬浮的铜的形成。在这项工作中,提出了有关铜形态与流体介电性能之间相关性的研究。特别是,为了确定油中的总铜含量,从而通过减去颗粒状铜的存在来区分,我们优化了一种油矿化方法。此外,通过用PTFE过滤器(0.45、1和5; C; m)过滤机油,可以量化和区分悬浮铜含量的尺寸,并与溶解的铜相区分:这样,我们研究了颗粒状铜对铜的影响。油的特性,我们确定了主要影响介电性能的物理形式。