Copper sulfide deposition on cellulosic insulating materials in oil-immersed transformers is evaluated by heating tests stipulated by IEC 62535. Although this method is suitable for evaluation of the corrosivity of unused insulating oil, the subject remains in diagnosis of the insulating oil used. It is because dibenzyl disulfide (DBDS), which is the prime compounds that cause copper sulfide deposition, is consumed by the reaction with copper during operating of transformer. Therefore, it is necessary to detect the existence of DBDS in insulating oil diagnosed as non-corrosivity by IEC 62535. The proceeding paper [6] reports that Bibenzyl (BiBz) and Dibenzyl sulfide (DBS) will be formed in the insulating oil as by-products of copper sulfide formation between copper and DBDS in oxygen-poor atmosphere which imitated the closed-type transformers. These by-products are considered to be the indication of copper sulfide formation. However, the influence of oxygen and addition agent (e.g. 2,6-di-tert-butylp- cresol) on the mechanism of the by-product formation is unclear. The purpose of this study is to elucidate the influence of oxygen and DBPC in by-products formation for development of diagnosis. It became apparent that benzyl alcohol, benzaldehyde and benzoic acid generate as by-products of copper sulfide formation in the air atmosphere which imitated the open-breathing transformers. Furthermore, it became apparent that the reaction product of benzyl radical and the radical of DBPC generates as by-product of copper sulfide formation in the insulating oil containing DBPC. These by-products are detectable even if DBDS disappears. Therefore, it is thought that diagnosis of the open-breathing transformer is possible by detecting these by-products.
机译:油浸式变压器中纤维素绝缘材料上的硫化铜沉积是通过IEC 62535规定的加热测试进行评估的。尽管该方法适用于评估未使用的绝缘油的腐蚀性,但仍然需要对所使用的绝缘油进行诊断。这是因为在变压器运行过程中与铜的反应会消耗二硫化二苄基(DBDS),这是导致硫化铜沉积的主要化合物。因此,有必要检测被IEC 62535诊断为非腐蚀性的绝缘油中DBDS的存在。论文[6]报告说,绝缘油中会形成联苄基(BiBz)和二苄基硫醚(DBS),就像通过贫氧环境中,铜与DBDS之间形成硫化铜的产物,模仿了封闭式变压器。这些副产物被认为是硫化铜形成的迹象。但是,氧和添加剂(例如2,6-二叔丁基对甲酚)对副产物形成机理的影响尚不清楚。这项研究的目的是阐明氧气和DBPC在副产物形成中对诊断发展的影响。显而易见的是,在空气中,苄醇,苯甲醛和苯甲酸作为硫化铜形成的副产物而产生,其模仿了开放式呼吸变压器。此外,显而易见的是,苄基自由基与DBPC自由基的反应产物在含有DBPC的绝缘油中作为硫化铜形成的副产物而生成。即使DBDS消失了,也可以检测到这些副产物。因此,认为可以通过检测这些副产物来诊断开式呼吸变压器。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号