首页> 外文期刊>MATEC Web of Conferences >Study of Capacitor Bank Switching Transient in Distribution Network
【24h】

Study of Capacitor Bank Switching Transient in Distribution Network

机译:配网电容器组切换暂态的研究

获取原文
       

摘要

The power factor improvement has a great concern in the distribution system due to large motor installed in industrial system. The capacitor bank was installed to improve the power factor in the distribution system. Due to frequently capacitor bank switching has create transient phenomena in the distribution system and their effects the power quality. The aims of this research to study and simulate the effects of capacitor bank switching in the distribution system. The simulation has been conduct with PSIM software by modelled the system which contain of supply, load and three capacitor bank. The simulation was conducted with two conditions which are single bank and bank to bank switching. For single bank switching peak voltage of phase R reached about 60.9 kV and peak inrush current is reached about 6.7 kA. While for bank to bank switching the peak voltage of phase R reached as high as 59 kV and the peak inrush current is almost 8.2 kA.
机译:由于工业系统中安装了大型电动机,因此功率因数改善在配电系统中引起了极大关注。已安装电容器组以改善配电系统中的功率因数。由于电容器组的频繁开关,在配电系统中产生了瞬态现象,并影响了电能质量。本研究的目的是研究和模拟配电系统中电容器组切换的效果。通过使用PSIM软件对系统进行建模,该系统包含电源,负载和三个电容器组。模拟是在两个条件下进行的,即单排和排到排的切换。对于单排开关,R相的峰值电压达到约60.9 kV,峰值浪涌电流达到约6.7 kA。对于组间切换,R相的峰值电压高达59 kV,峰值浪涌电流接近8.2 kA。