The Skinny on Switchgear and the New NEC

机译:开关设备的瘦身和新NEC

获取原文
获取原文并翻译 | 示例
           

摘要

It must be understood that the short time delay from not having an instantaneous trip can allow fault currents to flow for several cycles (typically up to 30 cycles), which can subject the electrical system to high mechanical and thermal stresses. The system equipment must also be coordinated to ensure it can withstand this tripping time delay. Switchboard construction will handle its rated fault current for only three cycles, while switchgear construction can handle its rated fault current for 30 cycles. There is, however, one particular manufacturer that I know of who makes a hybrid type of switchboard that will handle the rated fault current for 30 cycles. But in general, if the engineer chooses to go the route of providing breakers with no instantaneous function, the system must use more expensive switchgear con-struction.
机译:必须理解的是,由于没有瞬时跳闸而导致的短时间延迟会导致故障电流流经多个周期(通常最多30个周期),这可能会使电气系统承受较高的机械应力和热应力。还必须协调系统设备,以确保它可以承受此跳闸时间延迟。配电盘结构只能处理三个周期的额定故障电流,而开关柜结构可以处理30个周期的额定故障电流。但是,据我所知,有一个特定的制造商是谁制造的混合型配电盘,可以处理30次循环的额定故障电流。但是总的来说,如果工程师选择不提供具有瞬时功能的断路器,那么系统必须使用更昂贵的开关柜结构。