首页> 外文期刊>Construction and Building Materials >Validation of size estimation of debonds in external wall's composite finishes via passive Infrared thermography and a gradient algorithm
【24h】

Validation of size estimation of debonds in external wall's composite finishes via passive Infrared thermography and a gradient algorithm

机译:通过被动红外热成像和梯度算法验证外墙复合饰面中脱胶剂的尺寸估算

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

This paper aims to present a study on validating a passive and quantitative infrared thermography (PQIRT) methodology to estimate the size of debond in rendered and tile composites in external walls of high-rise buildings. The accuracies of the PQIRT methodology were evaluated under four conditions, including (i) nine depths of debonds, (ii) three temperature ranges, (iii) two types of composites and (iv) changes of heat flux during a 2-h diurnal and continuous monitoring. The method processed infrared images with a simple spatial pixel differentiation algorithm to determine temperature gradients, where the absolute temperature value was no longer required. The methodology was validated by comparing the estimated and the actual sizes of the debonds by statistical error analysis. In the rendered composites, the percentage error was at most 15% for cover depths of debond up to 20 mm for all temperature ranges. In the tile composites, the error was at most 30% for cover depths of debond up to 9 mm at all temperature conditions, while the estimation was erroneous for cover depths beyond 9 mm. These results will form the basis to develop guidelines for using PQIRT for inspection of high-rise building envelops in densely populated cities, which supplement the current qualitative inspection adopted by a handful of few accredited laboratories in Hong Kong and elsewhere. (C) 2015 Elsevier Ltd. All rights reserved.
机译:本文旨在提出一项验证被动和定量红外热成像(PQIRT)方法的研究,以估算高层建筑外墙中粉刷和瓷砖复合材料中脱胶的大小。在四个条件下评估了PQIRT方法的准确性,其中包括(i)九个剥离深度,(ii)三个温度范围,(iii)两种类型的复合材料,以及(iv)在每天2小时的昼间热通量变化和持续监控。该方法使用简单的空间像素微分算法处理红外图像以确定温度梯度,而不再需要绝对温度值。通过统计误差分析比较脱胶的估计尺寸和实际尺寸,验证了该方法的有效性。在所提供的复合材料中,在所有温度范围内,对于最大20 mm的脱粘覆盖深度,百分比误差最多为15%。在瓷砖复合材料中,在所有温度条件下,剥离厚度不超过9 mm的覆盖深度的误差最大为30%,而覆盖深度超过9 mm的估算是错误的。这些结果将成为制定使用PQIRT来检查人口稠密城市中高层建筑围护结构的准则的基础,该准则将补充香港和其他地方的少数几个经过认可的实验室目前采用的定性检查。 (C)2015 Elsevier Ltd.保留所有权利。

著录项

  • 来源
    《Construction and Building Materials》 |2015年第15期|113-124|共12页
  • 作者单位

    Hong Kong Polytech Univ, Dept Civil & Environm Engn, Hong Kong, Hong Kong, Peoples R China|Hong Kong Polytech Univ, Dept Land Surveying & Geoinformat, Hong Kong, Hong Kong, Peoples R China;

    Hong Kong Polytech Univ, Dept Civil & Environm Engn, Hong Kong, Hong Kong, Peoples R China;

    Hong Kong Polytech Univ, Dept Civil & Environm Engn, Hong Kong, Hong Kong, Peoples R China;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Composite debond; High-rise building; Passive infrared thermography;

    机译:复合脱胶;高层建筑;被动红外热像仪;