A comparison study on using air-cooled and water-cooled conventional and oil-free chillers in hospitals in Hong Kong is reported. The study commenced with a comprehensive literature review to reaffirm the effectiveness of recommended precaution measures for containing the risk of Legionnaires' disease (LD) associated with using cooling towers. Numerical performance models for oil-free chillers established for use in the study are presented. Based on recorded cooling demands of two existing hospitals, the life-cycle energy consumption and cost of system options involving different combinations of heat rejection method and chiller type were evaluated, compared and discussed. The results show that water-cooled air-conditioning systems with conventional chillers and cooling towers are still more energy efficient than air-cooled systems with oil-free chillers. Water-cooled oil-free chillers may become an economically viable choice when their price is lowered in future. Pilot installation is recommendable, as it would allow the reliability and maintainability of the new oil-free chillers to be ascertained. Practical applications: Findings of the literature review reaffirmed the effectiveness of measures recommended in contemporary guidelines for LD prevention, which would ease the mind of owners, designers and operation and maintenance personnel in regard of using cooling towers in hospitals. The numerical models for oil-free chillers presented in the paper are useful for evaluation of the energy consumption of this new type of chiller and for comparison with other types of chillers. The study approach described in the paper, including the energy consumption prediction and life-cycle cost evaluation methods, provides a useful framework for similar studies.
机译:据报道,在香港的医院中使用风冷和水冷的常规和无油冷却器进行了比较研究。该研究首先进行了全面的文献综述,以重申建议的预防措施的有效性,该措施能有效地控制与使用冷却塔相关的军团病(LD)的风险。提出了用于研究的无油冷水机的数值性能模型。基于两家现有医院记录的制冷需求,评估,比较和讨论了涉及散热方法和冷却器类型不同组合的系统选项的生命周期能耗和成本。结果表明,使用常规冷却器和冷却塔的水冷式空调系统比使用无油冷却器的风冷式系统仍具有更高的能源效率。当将来降低价格时,水冷无油式冷水机可能会成为经济上可行的选择。建议进行先导安装,因为这样可以确定新型无油制冷机的可靠性和可维护性。实际应用:文献综述的结果再次确认了现代LD预防指南中推荐的措施的有效性,这将减轻所有者,设计者以及操作和维护人员在医院中使用冷却塔的意识。本文中提出的无油冷水机的数值模型对于评估这种新型冷水机的能耗以及与其他类型的冷水机进行比较非常有用。本文介绍的研究方法,包括能耗预测和生命周期成本评估方法,为类似研究提供了有用的框架。

著录项

  • 来源
  • 作者单位

    Department of Building Services Engineering, The Hong Kong Polytechnic University, Hunghom, Kowloon,Hong Kong SAR, China;

    Department of Health Technology and Informatics, The Hong Kong Polytechnic University, Hunghom,Kowloon, Hong Kong SAR, China;

    Department of Building Services Engineering, The Hong Kong Polytechnic University, Hunghom, Kowloon,Hong Kong SAR, China;

    Department of Building Services Engineering, The Hong Kong Polytechnic University, Hunghom, Kowloon,Hong Kong SAR, China;

    Hospital Authority, Hospital Authority Building, 147B Argyle Street, Kowloon, Hong Kong SAR, China;

  • 收录信息
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号