Aeration and gutter water levels in siphonic roof drainage systems

机译:虹吸屋顶排水系统中的曝气和排水沟水位

获取原文
获取原文并翻译 | 示例

摘要

An investigation is presented into how negative system pressures, the degree of aeration, and gutter water levels are affected by the number of outlets in a siphonic roof drainage system. The experimental results show that system pressures decrease if outlets are blocked. It is also shown that the depth of water above an outlet is strongly influenced by the negative pressure acting at the outlet. As the suction effect at the outlet increases, due to lower system pressures, more water and air will be drawn into the outlets and this will result in a corresponding increase in overall gutter water depth. The results also show that there is often built-in redundancy in multiple outlet siphonic systems experiencing lower-intensity rainfall events, and if one or two outlets were blocked, the system would still operate satisfactorily. A new outlet suppressor was trialled and this was shown to reduce gutter water levels by up to 58% at some positions in the gutter.
机译:虹吸式屋顶排水系统的出口数量如何影响系统的负压,曝气程度和排水沟水位的调查。实验结果表明,如果出口堵塞,系统压力会降低。还显示出出口上方的水深受到作用在出口上的负压的强烈影响。随着出口处吸力的增加,由于较低的系统压力,更多的水和空气将被吸入出口,这将导致总排水沟水深相应增加。结果还表明,在经历低强度降雨事件的多个出口虹吸系统中,通常存在内置冗余,并且如果阻塞一个或两个出口,系统仍将令人满意地运行。尝试了一种新的出口抑制器,结果表明,该抑制器可在排水沟中的某些位置将排水沟水位降低多达58%。