首页> 外文期刊>Building and Environment >Risk of cross-infection in a hospital ward with downward ventilation
【24h】

Risk of cross-infection in a hospital ward with downward ventilation

机译:通风向下的医院病房发生交叉感染的风险

获取原文
获取原文并翻译 | 示例
       

摘要

A two-bed hospital ward with one standing healthcare person and a ceiling-mounted lowimpulse semicircular inlet diffuser is simulated in a full-scale room. Tracer gas is used for simulating gaseous contaminants, and the concentration is measured at different air change rates and different postures of the patients. A textile partition between the beds, which is typical in a hospital ward, is used for protection of the patients in some of the experiments. Three different layouts of return openings are tested. One layout with one opening at the ceiling, another with four openings at the wall opposite to the inlet diffuser, and one with a high location of these four openings. The downward recirculating flow is on average parallel with the partition, and in most cases the partition does not decrease cross-infection. A high location of the four return openings decreases the risk of cross-infection.
机译:在一个全尺寸的房间中模拟了一个两张病房的病房,其中有一名站立的医护人员和一个吊顶式低脉冲半圆形进口扩散器。示踪气体用于模拟气态污染物,并以不同的换气速率和患者的不同姿势测量其浓度。在某些实验中,通常使用病床之间的床头之间的纺织品隔板来保护患者。测试了三种不同的回流口布局。一种布局在天花板上有一个开口,另一种布局是在与进气口扩散器相对的壁上有四个开口,而另一种布局在这四个开口的较高位置。向下的再循环流平均与隔板平行,并且在大多数情况下,隔板不会减少交叉感染。四个回流口的位置较高,可降低交叉感染的风险。