首页> 外文期刊>Building and Environment >On the applicability of the laminar flow index when selecting surgical lighting
【24h】

On the applicability of the laminar flow index when selecting surgical lighting

机译:选择手术照明时层流指数的适用性

获取原文
获取原文并翻译 | 示例
       

摘要

In modern operating rooms ultraclean air is supplied through the ceiling to prevent bacteria from entering an operating wound and cause infections. Operating lamps can disturb this flow of clean air. In this paper the accuracy of some aspects of the Laminar Flow Index of operating lamps was tested. The disturbance of the airflow was determined for different shapes and sizes of operating lamps in an isothermal situation. To accomplish this, an experimental study and a simulation study of a small room with an operating lamp were performed. The infection risk was found to be proportional to the projected surface area of the lamp. Although different lamp shapes resulted in a distinctly different flow pattern in the room, this did not affect the infection risk in a significant way. Operating lamps with a projected area smaller than 0.1 m~2 do not disturb the airflow at all in this particular setup.
机译:在现代手术室中,通过天花板供应超净空气,以防止细菌进入手术伤口并引起感染。运行中的灯会干扰这种清洁的空气流动。本文测试了工作灯层流指数某些方面的准确性。确定了等温情况下不同形状和大小的工作灯的气流扰动。为此,对带有操作灯的小房间进行了实验研究和模拟研究。发现感染风险与灯的投影表面积成正比。尽管不同的灯形导致房间内的流动方式明显不同,但这并没有显着影响感染风险。在这种特殊设置下,投影面积小于0.1 m〜2的工作灯完全不会干扰气流。

著录项

  • 来源
    《Building and Environment》 |2010年第9期|1976-1983|共8页
  • 作者单位

    Building Physics and Systems, Eindhoven University of Technology, P.O. Box 513, 5600 MB Eindhoven, the Netherlands;

    rnBuilding Physics and Systems, Eindhoven University of Technology, P.O. Box 513, 5600 MB Eindhoven, the Netherlands;

    rnBuilding Physics and Systems, Eindhoven University of Technology, P.O. Box 513, 5600 MB Eindhoven, the Netherlands;

    rnBuilding Physics and Systems, Eindhoven University of Technology, P.O. Box 513, 5600 MB Eindhoven, the Netherlands;

  • 收录信息
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    surgical lighting; wound infection; operating room ventilation; experiments; CFD;

    机译:手术照明;伤口感染;手术室通风;实验;差价合约;