首页> 外文期刊>Building and Environment >Soft-repair technique for solving inherent oversizing effect on multiple rooftop units in commercial buildings
【24h】

Soft-repair technique for solving inherent oversizing effect on multiple rooftop units in commercial buildings

机译:软修复技术可解决商业建筑中多个屋顶单元固有的过大尺寸效应

获取原文
获取原文并翻译 | 示例

摘要

Rooftop packaged air-conditioning units (RTUs) have been intensively utilized in commercial buildings for providing space heating and cooling. They serve over 60% of the commercial building floor space in the U.S. Specifically, oversizing is an inherent issue practically caused by over design of mechanical engineers. With field test studies, oversizing can be up to 100% leading to high energy penalty. Although there are locally advanced control technologies utilized to improve the overall efficiency performance of RTUs, they are invasive approaches to interrupt normal operations and require experienced service teams for preventative maintenance causing high cost installation and service costs. The article proposes a novel and non-invasive methodology for permanently reducing the oversizing caused by non-optimal design or faulty design called "soft-repair". The technique composes of coordination control and over sizing analysis to ultimately eliminate the fault impact without retrofitting original control. Control algorithms are systematically developed to mainly reduce oversizing effect utilizing simplified instantaneous building load for approximately quantify actual building load. With the control algorithm tested by a building simulation platform, the oversizing effect can be decreased at least 30% by comparing oversizing parameter signature of the original oversizing system with the improved results of soft-repair implementation because a suitable number and time operations of RTUs are automatically computed based on the actual building load and the soft-repair algorithm. With the decrease of the oversizing effect and energy penalty, the improve results lead to energy savings and extended life cycle of compressors, condenser fans and supply fans. (C) 2016 Elsevier Ltd. All rights reserved.
机译:屋顶式空调机组(RTU)已在商业建筑中大量使用,以提供空间供暖和制冷。它们为美国超过60%的商业建筑占地面积提供服务。具体而言,尺寸过大实际上是机械工程师过度设计所引起的固有问题。通过现场测试研究,尺寸过大可以达到100%,从而导致高能耗。尽管使用了本地先进的控制技术来提高RTU的整体效率,但是它们是中断正常运行的侵入性方法,需要经验丰富的服务团队进行预防性维护,从而导致高昂的安装和服务成本。本文提出了一种新颖的,非侵入性的方法,可以永久减少由非最佳设计或错误设计(称为“软修复”)引起的尺寸过大。该技术由协调控制和超大尺寸分析组成,最终消除了故障影响,而无需改装原始控制。系统地开发了控制算法,主要是利用简化的瞬时建筑负荷来大致量化实际建筑负荷,从而主要减小过大的影响。使用由建筑仿真平台测试的控制算法,通过比较原始超大尺寸系统的超大尺寸参数签名与软修复实现的改进结果,可将超大尺寸效果至少降低30%,因为RTU的数量和时间是合适的根据实际建筑物负荷和软修复算法自动计算。随着尺寸过大效应和能量损失的减少,改善的结果导致了节能,并延长了压缩机,冷凝器风扇和供应风扇的使用寿命。 (C)2016 Elsevier Ltd.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号