In order to analyze the cracking and aging reason of the silicone rubber current transformer (CT) insulation bushing used for 8 years from a 500 kV alternating current substation, characteristics including Fourier transform infrared (FTIR) spectroscopy, mechanical properties analysis, hardness, and thermo gravimetric analysis have been carried out. The FTIR results indicated that the external surface of the silicone rubber CT insulation bushing suffered from more serious aging than the internal part, fracture of side chain Si–C bond was much more than the backbone. Mechanical properties and thermal stability results illustrated that the main aging reasons were the breakage of side chain Si–C bond and the excessive cross-linking reaction of the backbone. This study can provide valuable basis for evaluating degradation mechanism and aging state of the silicone rubber insulation bushing in electric power field.
机译:为了分析从500 kV交流变电站使用8年的硅橡胶电流互感器(CT)绝缘套管的开裂和老化原因,特性包括傅里叶变换红外(FTIR)光谱,机械性能分析,硬度和热性能重量分析已经进行。 FTIR结果表明,硅橡胶CT绝缘套管的外表面比内部遭受更严重的老化,侧链Si-C键的断裂远比骨架更严重。力学性能和热稳定性结果表明,老化的主要原因是侧链Si-C键断裂和骨架过度交联反应。该研究可为评价硅橡胶绝缘套管在电力领域的降解机理和老化状态提供有价值的依据。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号