山东泰安抽水蓄能电站地下厂房潮湿及管道结露的分析及处理措施

     

摘要

电站地下厂房通风空调系统从2007年投入运行后,蜗壳层、水轮机层的管路结露严重。对电站运行工况进行了长期连续测试,结果表明:4—6月,结露现象较普遍,水管壁面温度低于环境空气的露点温度;7—8月,水管壁面温度高于环境空气的露点温度,结露现象基本消失。提出了具体的防结露措施:采用难燃型橡塑保温材料对部分管路进行保温;同时,根据季节选择适当的通风量,合理设计气流组织,相应开启不同数量的冷冻除湿机。%Since the operation of ventilation and air conditioning system of underground plants in 2007,the moisture condensation phenomenon occurs seriously on the pipeline.Performs the long-term and continuous test for operation condition of hydropower station.The result shows that condensation occurs commonly when surface temperature of water tube is lower than dew-point temperature of the ambient air from April to June,while this phenomenon vanishes basically from July to August since the surface temperature of water tube is higher than dew-point temperature of ambient air.Presents the following detailed anti-condensation measures, including performing the insulation on part of tubes with nonflammable material,selecting appropriate ventilation rate according to seasons,designing reasonable air distribution,and operating different numbers of refrigeration dehumidification machines.