首页> 外文学位 >Voltage security assessment with high penetration levels of utility-scale doubly fed induction generator wind plants.
【24h】

Voltage security assessment with high penetration levels of utility-scale doubly fed induction generator wind plants.

机译:实用规模双馈感应发电机风电厂高渗透水平的电压安全评估。

获取原文
获取原文并翻译 | 示例

摘要

The interconnection requirements set forth by FERC in order 661-A mandate the operation of wind plants within a power factor range of 0.95 leading/lagging. This operation drastically underutilized the reactive output of doubly fed wind turbines (DFIG). This work discusses the impact of utilizing the capability curve of DFIG based wind plants on steady state and dynamic power system operation. A test system is used to demonstrate that committing the full reactive capability of a DFIG park can increase system penetration levels. This additional reactive support was also found to improve post fault voltage profiles by damping oscillations and preventing overshoots immediately after being subjected to a disturbance. The utilization of extended reactive limits in voltage control may prevent system collapse.
机译:FERC在661-A号命令中提出的互连要求规定了风力发电机组在功率因数0.95超前/滞后范围内的运行。此操作严重利用了双馈风力涡轮机(DFIG)的无功输出。这项工作讨论了利用基于DFIG的风力发电站的能力曲线对稳态和动态电力系统运行的影响。使用测试系统来证明,落实DFIG园区的全部反应能力可以提高系统渗透率。还发现,这种附加的无功支撑可通过抑制振荡并在受到干扰后立即防止过冲来改善故障后的电压分布。在电压控制中利用扩展的无功限制可以防止系统崩溃。