This paper presents a field experience in condition monitoring of a power transformer using SFRA technique. A design based comparison approach of the SFRA test results is discussed in the paper. In order to verify the latest condition of the transformer, the SFRA test was complemented with DGA and PD tests. The SFRA test results indicated that there is an abnormality within the transformer windings. The PD test results confirmed this interpretation, where very large ultrasonic impulses were detected. A series of DGA tests have showed that there is an early stage degradation of the insulating paper, which may be associated with fault within the transformer windings. The field experience showed that the monitoring approach has been very useful in indicating the possible occurrence of failure within the transformer structure.
机译:本文介绍了使用SFRA技术进行电力变压器状态监测的现场经验。本文讨论了一种基于设计的SFRA测试结果比较方法。为了验证变压器的最新状态,SFRA测试辅以DGA和PD测试。 SFRA测试结果表明变压器绕组内存在异常。 PD测试结果证实了这种解释,其中检测到非常大的超声波脉冲。一系列DGA测试表明,绝缘纸在早期退化,这可能与变压器绕组内的故障有关。现场经验表明,监视方法在指示变压器结构内可能发生故障方面非常有用。