首页> 外文会议>Technology conferences 2012: Visualization, imaging and image processing; Modelling and simulation; Wireless communications >ON-SITE TEST AND INTERFERENCE ANALYSIS OF GNSS SIGNALS UNDER ULTRA HIGH VOLTAGE (UHV) TRANSMISSION LINE
【24h】

ON-SITE TEST AND INTERFERENCE ANALYSIS OF GNSS SIGNALS UNDER ULTRA HIGH VOLTAGE (UHV) TRANSMISSION LINE

机译:超高压输电线路下GNSS信号的现场测试和干扰分析

获取原文
获取原文并翻译 | 示例

摘要

Focusing on the electromagnetic compatibility dilemma between increasingly intensive high-voltage power grids and the use of global navigation satellite systems (GNSS) in China, this paper reviews the interference mechanism of high voltage transmission line first. A real on-site GNSS observation test was conducted under 1000 kV Southeast Shanxi-Nanyang-Jinmen transmission lines, the first operational UHV AC Transmission Demonstration Project in China. 20 GNSS stations were configured and a large volume of data were acquired and processed under live and offline situations. The test results indicated that both live and offline GNSS coordinates were in consistency with high positioning precisions and unlikely effected by UHV AC transmission line. Correlation between the distances of GNSS receivers and the electromagnetic interference of the UHV AC transmission line was unfound.
机译:着眼于高压电网日益密集的电磁兼容性困境和中国在全球导航卫星系统(GNSS)的使用,本文首先回顾了高压输电线路的干扰机理。在中国首个在役的特高压交流输电示范项目-山西-南阳-金门东南1000 kV输电线路下进行了实际的GNSS观测测试。配置了20个GNSS站,并在实时和离线情况下采集和处理了大量数据。测试结果表明,实时和离线GNSS坐标都具有较高的定位精度,并且不太可能受到特高压交流输电线路的影响。 GNSS接收器的距离与特高压交流输电线路的电磁干扰之间没有相关性。