首页> 外文会议>Modelling and simulation >FEATURE EXTRACTION FOR FERRORESONANCE PHENOMENA IN ELECTRIC POWER SYSTEM
【24h】

FEATURE EXTRACTION FOR FERRORESONANCE PHENOMENA IN ELECTRIC POWER SYSTEM

机译:电力系统失谐现象的特征提取

获取原文
获取原文并翻译 | 示例

摘要

In this study, the ferroresonance phenomena are considered under the modeling of the West Anatolian Electric Power Network of 380 kV in Turkey. The ferroresonance event is carried out using the switching to remove the loads at the end of the lines. In this sense, two different cases are taken. At first, the switching is applied at 0.5 second and the ferroresonance effects are observed between 0.5 and 1 second in terms of the voltage variations. As a result the ferroresonance case and steady state case before the ferroresonance are compared with each other using the Fourier transform techniques. Hence, the properties of the ferroresonance event, which are defined between the 125 and 250 Hz, are presented in the frequency domain.
机译:在这项研究中,根据土耳其380 kV西安纳托利亚电网的模型,研究了铁磁谐振现象。使用开关执行ferroresonance事件,以消除行尾的负载。从这个意义上讲,采用了两种不同的情况。首先,在0.5秒时施加切换,并且在电压变化方面在0.5到1秒之间观察到铁磁谐振效应。结果,使用傅立叶变换技术将铁磁谐振情况与铁磁谐振之前的稳态情况进行了比较。因此,在频率域中呈现在125到250 Hz之间定义的铁磁谐振事件的属性。