Fast transient loads of low voltage power cables

机译:快速瞬态负载低压电源线

获取原文
获取外文期刊封面目录资料

摘要

Fast transient loads are kiloampere current spikes that last several minutes. The most recognized standards for sizing US manufactured cables are ampacity tables published in the National Electrical Code [3]. These tables are only for steady-state loads. For occasional kiloampere spikes of several minutes' duration, the temperature responses of medium-voltage cables have been published in [1]. A method to quickly size medium-voltage conductors undergoing fast transient loads is presented in [2]. Herein, fast transient work extends these methods to cover low-voltage cables of US manufacture. Exponential functions are analytically derived in [1] that express temperature responses to step changes in cable currents. Formulas for coefficients and time constants are derived. In [1] and [2] cable manufacturers' data and other sources for physical properties are used to calculate the responses of four sizes of 5kV power cables to these current spikes. The tables listing the results are repeated here with their sizing procedure. Herein are developed temperature responses to current spikes carried by 600 volt cables, and 600V power cable sizing methods. Motors demanding fast transient loads, and variable-speed drives supplying them are also discussed.
机译:快速瞬态负荷是持续几分钟的千旋星目前的尖峰。美国制造电缆的最公认的标准是国家电气码中发表的空缺表[3]。这些表仅适用于稳态负载。对于偶尔的千旋盆峰值,持续时间几分钟,中压电缆的温度响应已发表于[1]。在[2]中,介绍了快速尺寸尺寸的中电压导体的方法。这里,快速瞬态工作扩展了这些方法以覆盖美国制造的低压电缆。指数函数在[1]中,在[1]中,该函数表达到电缆电流的步骤变化的温度响应。派生系数和时间常数的公式。在[1]和[2]电缆制造商的数据和用于物理性质的其他源来计算四个尺寸的5kV电力电缆的响应到这些当前尖峰。列出结果的表格在此进行调整过程重复。本文是由600伏电缆承载的当前尖峰的温度响应,以及600V电力电缆施胶方法。还讨论了要求快速瞬态负载的电动机和提供它们的可变速度驱动器。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号