This paper proposes a latest current differential protection technique for a three-phase power transmission system. A protective relay is designed for recognition and classification of faults in a three-phase transmission line using three-phase fault currents measured synchronously at two- buses which are located at two sides of the transmission line. The designed protective relay is based on the computation of the differential approximate coefficients of wavelet transform (DACWT) of three-phase fault currents which is utilized to recognize the fault, classify the faulty phase, and discriminate the external and internal faults in a transmission line. The designed protective relay has been tested comprehensively using MATLAB with modification of fault parameters. The performance of the protective relay is verified for symmetrical faults, unsymmetrical faults, external faults, low-impedance faults, and high-impedance faults. Moreover, the sensitivity of the protective relay is also ensured when the transmission line is connected with a three-phase power source at one-end only. Simulation outcomes authenticate the effectiveness of protective relay as the faults are recognized and the faulty phases are categorized in near about half-cycle from the instigation of fault.
机译:本文提出了一种用于三相电力传输系统的最新电流差分保护技术。保护继电器设计用于使用三相故障电流在位于传输线的两侧同步测量的三相故障电流的三相传输线中的故障识别和分类。设计的保护继电器基于用于识别故障的三相故障电流的小波变换(DACWT)的差分近似系数的计算,分类故障相位,并在传输线中区分外部和内部故障。设计的保护继电器已经通过MATLAB进行全面测试,具有故障参数的修改。保护继电器的性能验证了对称断层,不对称断层,外部故障,低阻抗故障和高阻抗故障。此外,当传输线仅在一端以三相电源连接时,还确保了保护继电器的灵敏度。仿真结果验证保护继电器的有效性,因为识别出故障,故障阶段在故障灌注中分类为接近半周期。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号