摘要

The two-phase ejector refrigeration cycle (TPERC) system with a two-throat nozzle ejector was investigated experimentally, and the entrainment ratio of the ejector and the COP of the system were compared with those of the ejector with Laval nozzle and its TPERC system respectively. The experimental results indicate that under the working condition of the evaporating/condensing temperatures 1°C/45°C, the entrainment ratio of the two-throat nozzle ejector with different geometric size is greater than that of the Laval nozzle ejector, the maximum increment of the entrainment ratio is about 18%, and the COP of the TPERC system with two-throat nozzle ejector is greater than that of the TPERC system with Laval nozzle ejector, the maximum increment of the COP is about 12%. Under the fixed evaporating temperature 1°C, the entrainment ratio of the two-throat nozzle ejector and the Laval nozzle ejector achieve the maximum as the condensing temperature is 45°C. Under the fixed condensing temperature 50°C, the entrainment ratio of the two types of ejectors achieves the maximum as the evaporating temperature is 3°C.
机译:用两喉部喷嘴喷射器的两相喷射器制冷循环(TPERC)系统分别实验研究,并与与拉伐尔喷嘴及其TPERC系统的喷射器的喷射器和该系统的COP的夹带比进行比较。实验结果表明,该蒸发的/工作状态冷凝温度1℃/ 45℃,用不同的几何尺寸的双喉部喷嘴喷射器的夹带比大于拉瓦尔喷嘴喷射器的更大,最大增量下的夹带比为约18%,且TPERC系统的具有两个喉喷嘴喷射器的COP比TPERC系统拉瓦尔喷管喷射器越大,COP的最大增量是12%左右。下固定蒸发温度1℃,由于冷凝温度是45℃的双喉部喷嘴喷射器的夹带比和拉伐尔喷嘴喷射器达到最大。下固定冷凝温度50℃,随着蒸发温度为3℃时的两种类型的喷射器的夹带比达到最大。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号