首页> 外文会议>Japan Society of Refrigerationg and Air Conditioning Engineers;IIR Gustav-Lorentzen Conference on Natural Fluids >The effect of tube diameters on evaporation heat transfer for ammonia falling liquid-film
【24h】

The effect of tube diameters on evaporation heat transfer for ammonia falling liquid-film

机译:管直径对氨落液膜蒸发热传递的影响

获取原文
获取外文期刊封面目录资料

摘要

The present study experimentally investigated evaporation heat transfer characteristics of ammonia fallingliquid-film on horizontal stainless smooth tubes. The test tubes have outer diameters of 19.1 mm, 34.0 mm,42.7 mm and 60.5 mm, respectively. Experiments were conducted using ammonia as the refrigerant at asaturation temperature of -5 °C, heat flux and film Reynolds number ranges of 3 to 20 kWm~(-2) and 100 to 500respectively. Falling film evaporation heat transfer coefficients decreased with increasing film Reynoldsnumbers and are affected by tube diameters. Measured heat transfer coefficients were higher than pool boilingheat transfer coefficients of the correlation of Jung et al. in all heat flux ranges.
机译:本研究实验研究了氨落下的蒸发传热特性 水平不锈钢光滑管上的液膜。 试管具有19.1mm,34.0mm的外径, 分别为42.7毫米和60.5毫米。 使用氨作为制冷剂进行实验 饱和温度-5°C,热通量和薄膜雷诺数为3至20kWm〜(-2)和100至500 分别。 下降膜蒸发传热系数随着薄膜雷诺的增加而降低 数字并受管直径的影响。 测量的传热系数高于池沸腾 Jung等人的相关系数的传热系数。 在所有热通量范围内。