The paper addresses the problems of digital modelling of MV networks with the focus on phenomena having a significant impact on the reliability of resulting data subsequently used for testing protection relays. In ATPDraw program the Ferranti current transformer (core-balance current transformer) model was developed that allows taking into account the composite error that is due to discrepancy of magnetic coupling between the cable cores and the secondary coil as well as to the magnetizing current of the transformer. The impact of higher harmonics in the supplying voltage on algorithm performance in pre- and fault conditions has been investigated as well. The test results obtained for data without mentioned disturbances have been compared with outcomes for faults in the system with current transformation errors and harmonics in the pre-fault MV network signals.
机译:本文介绍了MV网络的数字建模问题,重点对现象具有显着影响的现象对测试保护继电器的所得数据的可靠性。在ATPDraw程序中,开发了Ferranti电流互感器(核心平衡电流互感器)模型,允许考虑到由于电缆芯和次级线线圈之间的磁耦合的偏差以及磁化电流而导致的复合误差。变压器。还研究了在预和故障条件下对算法性能的供给电压的影响。已经将没有提到的干扰的数据获得的测试结果与系统中具有电流转换误差和预故障MV网络信号中的谐波的结果的结果进行了比较。