首页> 外文会议>IEEE Symposium on Business, Engineering and Industrial Applications >Thermal environment of natural ventilated preschool buildings in warm-humid climates
【24h】

Thermal environment of natural ventilated preschool buildings in warm-humid climates

机译:温湿度气候自然通风幼儿园的热环境

获取原文

摘要

This paper appraises the indoor thermal environment of two natural ventilated pre-school buildings in Shah Alam city, Selangor. The physical measurement and survey questionnaires on thermal comfort were conducted among the teachers. The results obtained showed that mean temperature and relative humidity of both pre-school buildings were exceeded the standard, while for air velocity was still in suggested standard. The calculated Prediction Mean Vote (PMV) for both pre-school buildings were 0.9 which indicate ‘slightly warm’ condition and 1.2 which indicate ‘warm’ condition, respectively. Predicted Percentage Dissatisfied (PPD) indices computed for both pre-school building was above than 20% was considered dissatisfied. The computed Thermal Sensation Vote (TSV) indicates that teachers considered the indoor thermal to be ‘neutral’ for both pre-school buildings. These findings show that calculated thermal states are not necessarily correlated to occupant's desired thermal state.
机译:本文评价了雪兰莪州沙阿姆城市两栋自然通风前建筑物的室内热环境。在教师中进行了热舒适度的物理测量和调查问卷。得到的结果表明,校准建筑物的平均温度和相对湿度超过了标准,而空气速度仍在提出标准。学前学建筑物的计算预测平均投票(PMV)为0.9,表明‘略微温暖’条件和1.2,其指示‘温暖’条件分别。预测百分比对前院建筑的不满意(PPD)指数超过20%被认为是不满意的。计算的热敏投票(TSV)表示教师认为是室内热量‘中性’适用于学前班建筑物。这些发现表明,计算的热状态不一定与乘员期望的热状态相关。