The 400 kV GutinasBrasov o/h line is located in a mountain area with rocky soil. Because of the thick ice covering the conductors, during the winter times, causing the shieldwire breaking, the shieldwires were dismantled in the sections 94100 and 130145, long time ago. Without the shielding screen of the shieldwires those sections were left open to be struck by lightning. To reduce the lightning impact surge arresters were installed in two stages, the 2006 one, for the section 130145 and the second one in 2013, for the section 94100. Based on the first stage experience numerous improvements were applied for the second stage. No more lightning caused outages were recorded from the date of the first stage finalizing (20062016). Compared to the previous outage situation stating 410 outages per year, a very clear conclusion was drawn: a performant solution to protect the lines without shieldwires against the lightning strikes. Some improvements were proposed to the arrester manufacturer to increase the arrester component safety.
机译:400 kV Gutinasbrasov O / H线位于带岩石土地的山区。由于厚厚的冰覆盖导体,在冬季时,导致盾丝断裂,屏蔽丝在94100和130145的部分中被拆除。如果没有盾丝的屏蔽屏,那么这些部分被闪电打开。为了减少闪电冲浪避雷器,避雷器安装在两个阶段,2006年,对于第130145节和2013年的第二个,对于第94100节。基于第一阶段经验,第二阶段施加了许多改进。从第一阶段最终确定的日期开始,没有更多的闪电引起的中断(20062016)。与以前的中断情况指向每年410个中断的情况相比,绘制了一个非常明确的结论:一种性能的解决方案,用于保护线路而没有遮挡雷击的线路。避雷器制造商提出了一些改进,以提高避雷器组件安全性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号