EFFECTS OF INDOOR VENTILATION AND AIR MIXING ON DISINFECTION EFFICACY OF UPPER-ROOM UVGI SYSTEM

机译:室内通风和空气混合对上室UVGI系统消毒功效的影响

获取原文

摘要

With a validated Computational Fluid Dynamics (CFD) method, this paper investigated the effects of room air exchange rate (ACR), and ceiling fan's operation on the disinfection efficacy of an upper-room ultraviolent germicidal irradiation (UR-UVGI) system. UR-UVGI disinfection efficacy was evaluated by the index called "fraction of microorganism remaining (FR)", which was the ratio of the volume-averaged concentration of airborne microorganisms calculated with the UVGI turned "on" (Con) to that calculated with UVGI turned "off" (Coff). Three ACRs (2 ACH, 4 ACH and 6 ACH), and four fan speeds(40 rpm, 80 rpm, 150 rpm and 235 rpm) at two directions (upward and downward) were considered in this investigation. According to the simulation results, UR-UVGI disinfection efficacy was determined by ACR, and could be further improved by using ceiling fan. On the other hand, ceiling fan's rotational direction showed a slight influence. In conclusion, it seems an appropriate application to use the UR-UVGI system with ACR of 2 ACH and fan speed of 150 rpm.
机译:用验证的计算流体动力学(CFD)方法,本文研究了房间空气交换率(ACR),并且在上室内ultraviolent杀菌辐射(UR-UVGI)系统的消毒效果吊扇操作的影响。 UR-UVGI消毒功效通过所谓的“微生物的分数剩余(FR)”的索引,这是与UVGI计算空气中的微生物的体积平均浓度的“接通”(CON)的比例进行评价,以与UVGI计算“关闭”(COFF)。三周的ACR(2 ACH,4 ACH和6 ACH),并且在两个方向(向上和向下)4个的风扇速度(40rpm下,80rpm下,以150rpm和235 rpm)的在本次调查进行了审议。根据模拟结果,UR-UVGI消毒功效通过ACR确定,并且可以通过使用吊扇得到进一步改善。在另一方面,吊扇的旋转方向呈小幅影响。最后,似乎合适的应用程序使用的UR-UVGI系统2 ACH的ACR和150rpm的风扇速度。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号