首页> 外文会议>International Conference on Insulating Materials, Material Application and Electrical Engineering >Analysis on Reason of Generator Set Complete Power Outage of a Hydropower Plant
【24h】

Analysis on Reason of Generator Set Complete Power Outage of a Hydropower Plant

机译:发电机组合推理水电站的原因分析

获取原文

摘要

There was a single-phase high resistance grounding fault on the outgoing line of a 110kV hydropower plant. As a result of the mismatch of protection setting values, misoperations happened outside of the main transformer protection area, which caused generator set complete power outage. This paper used RTDS to carry out simulation analysis on this fault, restored the development process of the fault and figured out the fault reason. Meanwhile, through the investigation and analysis on the configuration status of the main transformer backup protection from high voltage side and the neighborhood transformer protection of 110kV hydropower plants throughout the whole province, we concluded the irrationality of the protection configuration and proposed the solutions to it.
机译:110kV水电站的输出线上有一个单相高电阻接地故障。由于保护设定值不匹配,主变压器保护区域外部发生误操作,导致发电机设置完整的停电。本文采用RTD对此故障进行仿真分析,恢复了故障的开发过程,并找出了故障原因。同时,通过对高压侧的主要变压器备份保护的配置现状和邻域变压器保护在整个省份的110kV水电站的邻域变压器保护中,我们总结了保护配置的非理性,并提出了解决方案。