The City of Olathe, KS has been using ultraviolet (UV) light for over 20 years to disinfect waste-water effluent. The Olathe system was one of the first low pressure/low intensity UV systems installed in the state of Kansas. Two pilot-scale UV systems were tested at the treatment plant to compare the extent of fouling of their quartz sleeves. The pilot testing included a multi-phase process to establish the operation and maintenance requirements for each system. The first phase of the testing was conducted to validate the performance of the pilot system. The second phase of the testing was to conduct a fouling study. Results of the study indicated that after one week the sleeve transmittance was close to zero percent. The results of the fouling study were used to determine projected cleaning requirements for the new UV system. A baseline condition was established to allow a comparison to be made after new equipment is installed.
机译:奥拉瑟市,KS一直在使用超过20年的紫外线(UV)光,以消毒废水流出物。 Olathe System是在堪萨斯州安装的第一个低压/低强度UV系统之一。在治疗厂测试了两种先导尺度紫外线系统,以比较其石英套管的污垢程度。导频测试包括多相过程,以确定每个系统的操作和维护要求。进行测试的第一阶段以验证试验系统的性能。测试的第二阶段是进行污垢研究。研究结果表明,在一周后,套筒透射率接近零百分比。结束研究的结果用于确定新UV系统的预计清洁要求。建立基线条件以允许在安装新设备后进行比较。