Ac minimum flashover voltages and wave number of occurrence of local discharges prior to flashover on polluted insulators

机译:在污染绝缘体上闪过闪光灯之前,AC最小闪络电压和局部放电的波浪次数

获取原文

摘要

The relation between ac minimum FO voltages V? and voltage build-up rates B has been investigated with respect to the wave number of occurrence N of local discharges prior to FO. The results show that V? occurs when N equals N? (5~11); i.e. N? increase from 5 to 11 as the pollution levels increase, and is independent of lengths for a given width. Additionally, similar informations are obtained for the cyclic number of ac minimum reignition voltages in contaminated conditions. It is also shown that the relation between the minimum FO voltages and the wave number of occurrence of local discharges is able to explain qualitatively with respect to the accumulation of Na atoms in discharge space at FO.
机译:AC最小v v v v的关系V?已经研究了电压积聚速率B,相对于在FO之前的局部放电的局部N的波浪数进行研究。结果表明V?当n等于n时发生? (5〜11);即n?随着污染水平的增加,从5到11增加,并且与给定宽度的长度无关。另外,获得类似的信息,用于污染条件中的循环数量的AC最小重新开始电压。还示出了最小Fo电压与局部放电的波浪之间的关系能够对FO的放电空间中的Na原子的积累进行定性地解释。