In this paper, an experimental apparatus of air source heat pump water heater (ASHPWH) usingR290 as working fluids was established in a climatic chamber to evaluate its performance andapplication feasibility. The air source heat pump water heater increased the water temperature up to70°C at working conditions of 0°C, to 65 °C and 55 °C at working conditions of -7°C and -15°C,respectively, without coefficient of performance (COP) decreasing compared to the typical range ofASHPWH. Among all the testing conditions, the maximum discharge pressure of the compressor is3.11MPa, the maximum discharge temperature is 98.8°C, and the maximum pressure ratio is 8.1,which are in the valid operating range of the compressor. The influence of refrigerant charge andcapillary tube length on the system performance were also investigated, results show that thesuitable charge not only increases COP, but also reduces pressure ratio and discharge temperature.