This paper presented an experimental investigation on CO2air conditioning cycles using minichannel evaporator with an internal heat exchanger (cycle A) and without an internal heat exchanger (cycle B). The cycles were experimented under the ambient temperature around 31 °C. The pressure of system was adjusted by an expansion valve. The cooler pressure increases from 75 to 78 bar. The evaporator pressure decreases from 45 to 42 bar. The mass flow rate is around 113.4 kg/h. The results show that the temperature before expansion process of cycle A is lower than that obtained from the cycle B from 1 to 2 °C. Besides, the evaporator temperature of cycle A is lower than that obtained from the cycle B also. However, the COP of both cycles is approximately the same (COP 6.55).
机译:本文提出了对CO的实验研究 2 使用带内部热交换器的微型通道蒸发器(循环A)和不带内部热交换器的微型通道蒸发器(循环B)进行空调循环。在约31°C的环境温度下对循环进行了实验。系统的压力由膨胀阀调节。冷却器压力从75巴增加到78巴。蒸发器压力从45 bar降低到42 bar。质量流率约为113.4 kg / h。结果表明,在1-2℃下,循环A的膨胀过程之前的温度低于从循环B获得的温度。此外,循环A的蒸发器温度也低于从循环B获得的温度。但是,两个循环的COP大致相同(COP 6.55)。