A very fast unblocking scheme for distance protection to detect symmetrical faults during power swings

机译:一种非常快速的疏通方案,用于距离保护,可在功率波动期间检测对称故障

获取原文

摘要

Power swing blocking function in distance relays is necessary to distinguish between a power swing and a fault. However the distance relay should be fast and reliably unblocked if any fault occurs during a power swing. Although unblocking the relay under asymmetrical fault conditions is straightforward based on detecting the zero- or negative-sequence component of current but symmetrical fault detection during a power swing presents a challenge since there is no unbalancing. This paper presents a very fast detection method used to detect symmetrical faults occurring during a power swing. Based on a 50 Hz component getting on three-phase active power after symmetrical fault inception and using Fast Fourier Transform (FFT), the proposed detection method can reliably and quickly detect symmetrical faults occurring during power swing in one power cycle, i.e. 0.02 second. This detection method is easy to set and immune to the fault inception time and fault location. Power swing and fault conditions are simulated by using software PSCAD/EMTDC®. FFT is performed by using On-Line Frequency Scanner block included in the software.
机译:距离继电器中的功率摆幅阻止功能对于区分功率摆幅和故障是必不可少的。但是,如果在动力摆幅过程中发生任何故障,则距离继电器应快速且可靠地解锁。尽管基于检测电流的零序或负序分量,在非对称故障条件下对继电器进行解锁是很简单的,但是由于没有失衡,因此在功率摆幅期间进行对称故障检测仍然是一个挑战。本文提出了一种非常快速的检测方法,用于检测在功率摆幅期间发生的对称故障。基于对称故障发生后50 Hz分量进入三相有功功率并使用快速傅里叶变换(FFT),该检测方法可以可靠而快速地检测到一个功率周期(即0.02秒)的功率摆幅期间发生的对称故障。这种检测方法易于设置,并且不受故障起始时间和故障位置的影响。使用软件PSCAD / EMTDC ®可以模拟功率摆幅和故障情况。通过使用软件中包含的在线频率扫描器模块来执行FFT。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号