首页> 外文会议>Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES >Using of parameters of RVM measurement for qualitative appreciation of power transformers insulation state
【24h】

Using of parameters of RVM measurement for qualitative appreciation of power transformers insulation state

机译:利用RVM测量参数对电力变压器绝缘状态进行定性评估

获取原文
获取外文期刊封面目录资料

摘要

The measurements of dielectric properties of high voltage equipment insulation in service conditions have seen a new renaissance during the past decade. The specific method of recovery voltage measurement called RVM is one from the commercially widely spread. The method is well known but the interpretation of test results is still subject of evolution and discussion. This paper contributes to this topic by a discussion on sensitivity of RVM parameters (main time constant and initial slope of recovery voltage) to moisture content and ageing degree of paper-oil insulation of power transformers. Test results from RVM measurements on 60 power transformers in service are presented in this paper. This data is compared with measurements of degree of polymerisation of paper samples, with service age of power transformers and with measurements of water content or in fact measurements of change in water content during drying.
机译:在过去的十年中,在使用条件下对高压设备绝缘的介电性能进行测量的新进展。恢复电压测量的特定方法称为RVM,是一种从商业上广泛使用的方法。该方法是众所周知的,但是对测试结果的解释仍然是发展和讨论的主题。本文通过讨论RVM参数(主时间常数和恢复电压的初始斜率)对水分含量和电力变压器纸-油绝缘的老化程度的敏感性,为这一主题做出了贡献。本文介绍了在用的60台电源变压器的RVM测量结果。将该数据与纸样品聚合度的测量结果,电力变压器的使用寿命以及水含量的测量结果进行比较,或者与干燥期间水含量变化的测量结果进行比较。