A data-driven analysis of lightning-initiated contingencies at a distribution grid with a PV farm using Micro-PMU data

机译:使用Micro-PMU数据的PV农场分发网格的闪电发起的抗吐纱的数据驱动分析

获取原文

摘要

In this paper, we conduct a data-driven experimental analysis of lightening-induced contingencies at a distribution grid in Riverside, CA, using data from three distribution level phasor measurement units, a.k.a, Micro-PMUs. The data was collected during four hours of a rainy day with several lightening strikes on October 24, 2016. Of particular interest was to analyze the impact and the response of a 7.5 MW PV farm. Due to the use of three Micro-PMUs, including one in an outlying area, we are able to distinguish system-wide events across the sub-transmission network against local events at the PV farm and its associated substation. Multiple interesting observations are made and the related causes are discussed. For example, based on the analysis of phase angle difference data, we observe that during at least one of the lightening events, there was a reverse power flow from the PV site to the substation due to a transient short-circuit caused by the surge arresters. This paper takes a first step in using Micro-PMU data to conduct a detailed analysis of how distributed energy resources (DERs) could be affected and and/or respond to the lightening-induced contingencies in distribution systems.
机译:在本文中,我们使用来自三个分布级别定量测量单元,A.K.A,微疗法的数据,对河滨,CA的分配网格进行了数据驱动的诱导的抗困境。在2016年10月24日的几个淡化罢工中,在雨天的四个小时内收集了数据。特别感兴趣的是分析7.5 MW PV农场的影响和反应。由于使用三个微量PMU,包括一个在偏远区域,我们能够在PV农场和其相关变电站的本地事件中区分跨子传输网络的系统范围内的事件。进行多次有趣的观察,并讨论相关原因。例如,根据相位角差数据的分析,我们的闪电事件中的至少一个期间观察到,有从PV站点到变电站的反向功率流,由于所引起的电涌放电器的瞬时短路。本文采用微量PMU数据进行详细分析分布式能源(DERS)如何影响和/或响应分配系统中的闪电诱导的突发事件的详细分析。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号