Transmission grids are generally designed and operated in accordance with deterministic N-1 criteria. These have ensured adequate reliability in the past in large measure because of existing margins in the system. These margins have generally been sufficient to retain system reliability in the face of N-2 disturbances such as simultaneous outages of parallel lines caused by proximity or relay miss-operation. In the US, operating margins against events "beyond criteria" are being eroded by various means such as the use of parallel flow balancing devices, new generators placed to utilize the existing system, and pressure from transmission users to increase transfer limits. Flows on parallel paths are being equalized towards maximum capability making ever-larger numbers of N-2 events critical events, increasing the risk for serious trouble not recognized by present criteria. An effective means of recognizing and protecting against events not covered by N-1 criteria are needed.
机译:传输网通常根据确定性的N-1标准进行设计和操作。由于系统中已有余量,这些在很大程度上确保了过去足够的可靠性。这些裕度通常足以在面对N-2干扰(例如由接近或继电器误操作引起的并行线路同时中断)时保持系统可靠性。在美国,各种“超出标准”事件的营业利润正在通过各种手段侵蚀,例如使用平行流平衡装置,放置使用现有系统的新发电机,以及传输用户增加传输限制的压力。并行路径上的流量正朝着最大能力均衡,从而使N-2事件越来越多地成为严重事件,从而增加了当前标准无法识别的严重故障的风险。需要一种有效的方法来识别和防御N-1标准未涵盖的事件。