首页> 外文会议> >Analysis of stator ground protection schemes for hydro-generator of Three-Gorges power plant based on zero sequence voltages
【24h】

Analysis of stator ground protection schemes for hydro-generator of Three-Gorges power plant based on zero sequence voltages

机译:基于零序电压的三峡水电厂水轮发电机定子接地保护方案分析

获取原文

摘要

New mathematical models for the zero-sequence voltage of large hydro-generator on turn basis are used to study hydro-generator stator ground fault protection schemes in this paper. The evaluation and the comparison of the characteristics of some stator ground protection schemes are described by means of protection coverage-critical resistance curves. And the simulation results showed that those schemes would suffer low sensitivity when they are used to huge hydro-generators in Three-Gorges power plant. To overcome this disadvantage, new ground fault protection schemes with higher sensitivity based on fault components are developed in this paper.
机译:本文以大型水轮发电机零序电压的新数学模型为基础,研究了水轮发电机定子接地保护方案。通过保护覆盖-临界电阻曲线描述了一些定子接地保护方案的性能评估和比较。仿真结果表明,这些方案用于三峡电厂大型水轮发电机时,灵敏度较低。为了克服这个缺点,本文开发了基于故障分量的具有更高灵敏度的新接地故障保护方案。