首页> 外文会议> >Influence of puffer volume and operating force on puffer pressure built up in thermal puffer type gas circuit breaker taking nozzle ablation into account
【24h】

Influence of puffer volume and operating force on puffer pressure built up in thermal puffer type gas circuit breaker taking nozzle ablation into account

机译:考虑喷嘴消融的吹气量和操作力对热吹气式气体断路器中积累的吹气压力的影响

获取原文

摘要

In order to investigate the influence of puffer volume V/sub P/ and operating force to dielectric performance of GCB at current interruption, we calculated the prospective dielectric withstand voltage V/sub W/ between arcing contacts. The withstand voltage was calculated by the electric field strength appearing on arcing contacts and the allowable electric field strength E*/sub W/ of hot gas due to thermal puffer action. We clarify that large initial puffer volume V/sub P/ can increase withstand voltage V/sub W/ at current breaking point and also that an optimum point exists in operating force F. For example, it was found that in case of the operating force of 1000 kgf, the puffer volume V/sub P/ of 1.2 liter would be best choice in the interrupting condition of i=50 kA and arcing time of 1.35 cycle.
机译:为了研究在中断电流时吹风量V / sub P /和操作力对GCB介电性能的影响,我们计算了电弧触头之间的预期介电耐压V / sub W /。通过在电弧触点上出现的电场强度和由于热吹风作用产生的热气的允许电场强度E * / sub W /来计算耐压。我们弄清楚,较大的初始吹风量V / sub P /可以在电流断点处增加耐压V / sub W /,并且在操作力F中存在一个最佳点。例如,发现在操作力的情况下当i = 50 kA的中断条件和1.35个周期的起弧时间时,最好选择1000 kgf的鼓风量V / sub P /为1.2升。