首页> 外文会议> >Configuration and reliability of an air-conditioning system for telecommunications systems that uses the heat dissipated from fuel cells
【24h】

Configuration and reliability of an air-conditioning system for telecommunications systems that uses the heat dissipated from fuel cells

机译:使用燃料电池散发的热量的电信系统空调系统的配置和可靠性

获取原文

摘要

NTT Power and Building Facilities Inc., is now developing an air conditioning system for telecommunications use that uses the heat dissipated from phosphoric acid fuel cells. The authors have investigated the reliability of the air conditioning system and have found that the reliability of such a system can be improved if either multiple absorption refrigerators are used, or if a back-up heat supply facility (burner) is installed in an absorption refrigerator. They have also found that both an exhaust heat-driven air conditioning system and an electrically driven distributed air conditioning system must be combined to meet the reliability level required of air conditioning for telecommunications systems. In such a configuration, the number of air conditioners in the electrically driven distributed air conditioning system can be reduced by 30%.
机译:NTT Power and Building Facilities Inc.现在正在开发一种用于电信的空调系统,该系统利用磷酸燃料电池散发的热量。作者研究了空调系统的可靠性,发现如果使用多个吸收式制冷机,或者在吸收式制冷机中安装备用供热设施(燃烧器),则可以提高这种系统的可靠性。 。他们还发现,必须结合使用排热驱动的空调系统和电动分布式空调系统,以满足电信系统空调所需的可靠性水平。在这种配置中,电动分布式空调系统中的空调数量可以减少30%。