首页> 外文会议>International Symposium on High Voltage Engineering; 20050825-29; Beijing(CN) >A Countermeasure of Simultaneous Double Circuit Trip of 154 kV Transmission Line by Lightning Current
【24h】

A Countermeasure of Simultaneous Double Circuit Trip of 154 kV Transmission Line by Lightning Current

机译:154 kV输电线路雷电电流同时跳闸的对策。

获取原文

摘要

It has been reported that more than 60% of transmission line faults occurs due to lightning strokes. To protect transmission lines from lightning stroke, reduction of tower footing resistance, multiple ground wires and unbalanced insulation in double circuit lines, have been generally considered. In Korea Electric Power Corporation most of transmission lines are double circuit transmission lines. At summer peak load, there are many simultaneous double circuit trips in KEPCO. The general method is often not effective to prevent the simultaneous trip faults. And we have found out that to attach parallel line arrester in the insulator string of the one circuit is the best way to eliminate the double circuit trip. We installed 90 line arresters in a 154 kV double circuit line. The air gap of a line arrester is 630 mm whereas the arcing horn gap of insulators string of 154 kV transmission line is 1120 mm. By EMTP simulation, lightning discharge current follows through the line arrester in a few to 10s microseconds and extinguished. After a few years' operation, there is no double circuit trip in the line arrester installed section.
机译:据报道,超过60%的传输线故障是由雷击引起的。为了保护传输线免受雷击,通常考虑降低铁塔立柱电阻,降低多根地线以及在双回线中的绝缘不平衡。在韩国电力公司中,大多数传输线是双回路传输线。在夏季高峰负荷​​时,KEPCO会同时发生许多双回路跳闸。通用方法通常不能有效地防止同时发生跳闸故障。并且我们发现,在一个电路的绝缘子串中安装并联避雷器是消除双重电路跳闸的最佳方法。我们在154 kV双回路线路中安装了90个线路避雷器。避雷器的气隙为630 mm,而154 kV输电线路的绝缘子串的弧形喇叭间隙为1120 mm。通过EMTP仿真,雷电放电电流在几到10微秒内流过避雷器,然后熄灭。经过几年的运行,线路避雷器的安装部分没有出现双回路跳闸。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号