Electric Potential Assessment Due to Lightning Strike into the Overhead Ground Wire in Power Distribution System

机译:配电系统中因雷电侵入架空地线而产生的电势评估

获取原文

摘要

This paper focuses on assessment of the electric potential (EP) due to lightning strike into the overhead ground wire (OHGW) in power distribution line. Power distribution line and substation of provincial electricity authority (PEA) model used in the current distribution electromagnetic interference grounding and soil structure (CDEGS) program has five models. For simulation of lightning current, the lightning impulse waveforms according to IEC 62305-1. Waveforms have a time interval of 0.25/100 μs and 10/350 μs generated in the CDEGS program for lightning current testing. Lightning current with a peak value of 34.40 kA is the value of lightning current in Thailand. The study results confirmed that connect the OHGW (case 4) is an effective way to help decrease the EP.
机译:本文着重评估因雷击进入配电线路中的架空地线(OHGW)而引起的电势(EP)。在当前配电电磁干扰接地和土壤结构(CDEGS)程序中使用的省电力管理局(PEA)模型的配电线路和变电站具有五个模型。为了模拟雷电流,根据IEC 62305-1的雷电脉冲波形。在CDEGS程序中生成的波形间隔为0.25 / 100μs和10/350μs,用于雷电流测试。峰值为34.40 kA的雷电流是泰国的雷电流值。研究结果证实,连接OHGW(案例4)是帮助降低EP的有效方法。