摘要

For distribution systems, transition resistances affect the fault current greatly, especially when the single phase to ground fault occurs. Since the fault currents varies with different values of transition resistances, it is suggested to utilize the inverse time overcurrent relays in protection process. For neutral point ineffective grounding systems, a smart grounding device is recently proposed to be installed. This device can add a small resistance to the neutral point and multiplies the fault current for easier protection. Under such circumstances, this paper utilizes the Exhaustive Search based method to obtain the optimal settings of the relays. The selectivity and the speed of the relays are demonstrated through a 10KV distribution system.
机译:对于配电系统,过渡电阻会极大地影响故障电流,尤其是在发生单相接地故障时。由于故障电流随过渡电阻值的不同而变化,因此建议在保护过程中使用反时限过电流继电器。对于中性点无效的接地系统,最近建议安装智能接地设备。该设备可以给中性点增加一个小的电阻,并使故障电流倍增,从而更易于保护。在这种情况下,本文利用基于穷举搜索的方法来获得继电器的最佳设置。通过10KV配电系统演示了继电器的选择性和速度。