Lines with common-terminal is an economic and practical erection form in the multi-circuit transmission system, which also presents extra challenges to the protection. The feature of cross-line fault on common-terminal lines and its impact on the protection principle are discussed in this paper. Theoretical analysis shows that sound phase can also exhibit fault feature, under the effect of fault phase in the neighboring line. Furthermore, combined with inter-phase measured impedance (IPMI) expression derived in this paper, the operation characteristic of different distance relays are discussed by their setting range. For the loop only has one fault phase, the risk of maloperation is extremely high when fault is nearing the protection installation. The accuracy of theoretical analysis is verified by the validation tests in PSCAD.
机译:在多回路传输系统中,具有公共端子的线路是一种经济实用的架设形式,这也给保护带来了额外的挑战。讨论了公共终端线路交叉线路故障的特点及其对保护原理的影响。理论分析表明,在相邻线路故障相的作用下,声相也可表现出故障特征。此外,结合本文推导的相间测量阻抗(IPMI)表达式,通过设定范围来讨论不同距离继电器的工作特性。因为环路只有一个故障阶段,所以当故障接近保护装置时,发生误操作的风险非常高。理论分析的准确性已通过PSCAD中的验证测试得到验证。