摘要

In order to reduce the construction cost of 500kV substation and improve the design reliability, it is necessary to study the discharge characteristics of typical air gaps. In this paper, the discharge tests of bundle conductor to herringbone frame air gap of UHV substation were carried out in Beijing (0m above sea level, 0m a.s.l) and Tibet (4300m a.s.l). The discharge characteristic curves of AC, switching impulse and lightning impulse were obtained. Then, using the existing altitude correction methods, the calculated value and the tested value of altitude correction factor were compared and analyzed. Finally, using the linear interpolation method, the discharge characteristic curve in the range of 1000m-5000m above sea level was obtained, and the minimum air gap distance was recommended. The research results can be used to guide the engineering design of UHV substation in high altitude areas, and it is also great significant to the design, construction and operation of other power transmission projects in high altitude areas.
机译:为了降低500kV变电站的建设成本,提高设计的可靠性,有必要研究典型气隙的放电特性。本文在北京(海拔0m,海拔0m a.s.l)和西藏(海拔4300m a.s.l)进行了特高压变电站的束状导体至人字形气隙的放电试验。获得了交流,开关脉冲和雷电脉冲的放电特性曲线。然后,使用现有的海拔校正方法,对海拔校正因子的计算值和测试值进行比较和分析。最后,采用线性插值法,获得了海拔1000m-5000m范围内的放电特性曲线,并建议了最小的气隙距离。研究结果可为高海拔地区特高压变电站的工程设计提供指导,对高海拔地区其他输电工程的设计,施工和运行也具有重要意义。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号