首页> 外文会议>International Conference on Power System Technology >Analysis of Arc Suppression Performance of Active Transfer Type Arc Extinguishing Device
【24h】

Analysis of Arc Suppression Performance of Active Transfer Type Arc Extinguishing Device

机译:主动转移式消弧装置消弧性能分析

获取原文

摘要

In this paper, considering the influence of line voltage drop, the arc extinguishing performance of the active transfer type arc-extinguishing device is further analyzed. The expression of single-phase ground fault point current is derived by the theory of symmetrical component method. The simulation verified the correctness of the theoretical analysis based on ATP/EMTP. The results show that when the active transfer type arc extinguishing device is applied to long feeders and heavy loads, if a low-resistance ground fault occurs, the current flowing through the ground fault point may increase, which is not conducive to the extinguishing of the arc at the fault point.
机译:本文考虑线电压降的影响,进一步分析了有源转移式消弧装置的消弧性能。通过对称分量法的理论推导了单相接地故障点电流的表达式。仿真验证了基于ATP / EMTP的理论分析的正确性。结果表明,将有源转移式灭弧装置应用于长馈线和重载时,如果发生低电阻接地故障,流经接地故障点的电流可能会增加,不利于灭火。在故障点起弧。