首页> 外文会议>International Conference on Power System Technology >Optimal Configuration of PMU Based on False Data Injection
【24h】

Optimal Configuration of PMU Based on False Data Injection

机译:基于虚假数据注入的PMU优化配置

获取原文

摘要

At present, the injection of false data (FDI) in power system network brings a direct challenge to state estimation and reduces the reliability of the system. The data collected by WAMS system is of high frequency and accuracy, which can effectively prevent FDI attacks. This paper focuses on the problem of PMU optimization configuration considering false data injection. On the premise of ensuring the overall observability of the system and taking the zero injection node into account, the effect of false data injection on the power grid is effectively reduced through the optimized configuration of PMU, and the accuracy of state estimation data is improved to the maximum extent. Taking IEEE14 IEEE30 and IEEE57 standard nodes as examples, the data accuracy was improved to the maximum extent with the minimum number of PMU, and the feasibility of the method was verified.
机译:当前,在电力系统网络中注入错误数据(FDI)给状态估计带来了直接挑战,并降低了系统的可靠性。 WAMS系统收集的数据具有很高的频率和准确性,可以有效地防止FDI攻击。本文着重于考虑错误数据注入的PMU优化配置问题。在保证系统整体可观察性的前提下,考虑零注入节点,通过优化的PMU配置,有效减少了虚假数据注入对电网的影响,提高了状态估计数据的准确性最大程度。以IEEE14 IEEE30和IEEE57标准节点为例,以最小的PMU数量最大程度地提高了数据精度,验证了该方法的可行性。