摘要

Artificial instantaneous grounding test of DC overhead lines is a key step to verify the high-speed DC circuit breakers' rapid breaking performance and the control and protection strategies of VSC-HVDC. This paper introduced the artificial grounding test method of first mechanical HVDC circuit breaker in CSG, PSCAD software was used to simulate the key parameters such as breaking current and LC oscillation current of DC circuit breaker. The field tests and simulation comparison show that arc extinguishing of mechanical fracture delays 3.5ms after receiving the DC protection action, and the cut-off current is 1370A, the arrester in DC circuit breaker did not act, and the LC oscillating current is fed into DC line. Subsequent applications should pay attention to the influence of the LC oscillating current of the mechanical HVDC breaker on the protection of VSC-HVDC.
机译:直流架空线路的瞬时瞬时接地测试是验证高速直流断路器的快速分断性能以及VSC-HVDC的控制和保护策略的关键步骤。介绍了CSG中第一个机械式HVDC断路器的人工接地测试方法,使用PSCAD软件模拟了直流断路器的分断电流和LC振荡电流等关键参数。现场测试和模拟比较表明,机械断裂的灭弧在受到直流保护作用后延迟了3.5ms,截止电流为1370A,直流断路器中的避雷器不起作用,LC振荡电流馈入直流线。后续应用应注意机械HVDC断路器的LC振荡电流对VSC-HVDC的保护的影响。