首页> 外文会议>International Conference on Power System Technology >Fault Characteristics and Protection Actions of Modular Multilevel Converter in 500kV Sunan UPFC
【24h】

Fault Characteristics and Protection Actions of Modular Multilevel Converter in 500kV Sunan UPFC

机译:500kV苏南UPFC模块化多电平变换器的故障特性及保护措施

获取原文

摘要

Unified Power Flow Controller (UPFC) project in Suzhou 500kV southern power grid is the highest voltage class and largest capacity UPFC project in the world, and it is used to solve the problems of uneven power flow distribution, over-limited sectional flow, poor dynamic reactive support ability, et al. In this paper, the fault characteristics of sub-modular, including open circuit, control pulse loss and falsely closed, and the converter protection of Modular Multilevel Converter (MMC) in 500kV Sunan UPFC project are discussed in detail. Fault simulation platform based on Matlab/Simulink is applied to analyze the corresponding relationship between several kinds of sub-modular faults and converter protection, which will be useful for operation and maintenance workers to locate fault area quickly.
机译:苏州500kV南方电网统一潮流控制器(UPFC)项目是世界上电压等级最高,容量最大的UPFC项目,用于解决潮流分布不均,断面流量过大,动态不佳的问题反应支持能力,等。本文详细讨论了500kV苏南UPFC项目中子模块的开路,控制脉冲损耗和误合闸等故障特征以及模块化多电平转换器(MMC)的转换器保护。应用基于Matlab / Simulink的故障仿真平台,分析了几种子模块化故障与变流器保护之间的对应关系,为运维人员快速定位故障区域提供了依据。