首页> 外文会议>International Conference on Power System Technology >Research on Ultra-Low Frequency Oscillation Caused by Hydro Power in Hydro-Dominant Power System
【24h】

Research on Ultra-Low Frequency Oscillation Caused by Hydro Power in Hydro-Dominant Power System

机译:水力发电系统中水力引起的超低频振荡的研究

获取原文

摘要

There is a rare frequency problem in the Southeast power grid which is with a high ratio of hydropower penetration. The prominent negative damping effect of hydro unit causing the emergence of ultra-low frequency oscillation (ULFO), the frequency of which is less than 0.1Hz has been studied. The detailed SMIB system of hydro unit based on linear hydraulic turbine model and the type-8 governing system in PSASP has been established. The main factors, which mostly influence the system damping level including water hammer effect and the operation level especially the output power of hydro unit have been researched. According to the simulation results, the dynamic characteristics of frequency responses and output active power fluctuation are analyzed and effects of the main factors on ULFOs are concluded. Finally, the proper suggestions on adjusting the hydropower scale and operation modes for hydro-dominant power system stability are proposed.
机译:东南电网中罕见的频率问题是水电渗透率很高。研究了水力单元引起频率小于0.1Hz的超低频振荡(ULFO)出现的显着负阻尼效应。建立了基于线性水轮机模型的水力机组SMIB详细系统和PSASP中的8型调节系统。研究了影响系统阻尼水平的主要因素,包括水锤效应和运行水平,尤其是水力机组的输出功率。根据仿真结果,分析了频率响应和输出有功功率波动的动态特性,并总结了影响ULFO的主要因素。最后,提出了调整水电规模和运行方式,以水电为主的电力系统稳定的适当建议。